| |
The first step when sizing for a ventilation fan is to determine
the application. Decide whether you are sizing for intermittent
or continuous ventilation. If intermittent, determine which application
i.e. bathroom, kitchen, or other. Use the following industry recommendations
to determine Air Changes per Hour (ACH) for your specific application.
Intermittent (Spot) Ventilation:
The Home Ventilating Institue (HVI) recommends the following Air
Changes per Hour (ACH).
- Bathrooms - 8 ACH
- Kitchen - 15 ACH
- Other Rooms - 6 ACH
Continuous (Whole House) Ventilation:
Many building codes have adapted the American Society of Heating and
Refrigerating and Air Conditioning Engineers (ASHRAE) Standard 62,
as show below.
- House of apartment - 0.35 ACH
Back to top |
| |
The second step is to calculate the are being ventilated. Calculate
square feet or cubic feet depending on which sizing method you choose.
Both methods, the Sizing Chart Method and the Performance Curve
Method, follow industry standards and will give you similar outcomes.
The Sizing Chart Method is easier. The Performance Curve Method
is often preferred by engineers.
Note: You should check with you local building inspector to confirm
that these methods are accepted in your area.
Sizing Chart Method
Example: Sizing for an 8 ft x 12 ft x
8 ft ceiling bathroom using 12-foot long, 4 inch diameter aluminum
flex duct, one elbow, one wall cap.
- Determine the ACH required for the given application
using the HVI or ASHRAE standards above
* Bathroom - 8 ACH
- Calculate the Area to be ventilated in Square Feet.
Assuming 8 foot ceiling: room length x width
* 8 ft x 12 ft = 96 sq. ft.
Guideline for cathedral ceilings:
i. 10 - 12 ft cathedral = length x width x 1.25
ii. 12 - 16 ft catherdal = lenth x width x 1.5
- Use the Equivalent Duct Length chart to calculate the
duct run.
i. 12 ft flex aluminum duct x 1.25 = 15 feet EDL
ii. One elbow jack equals 15 feet EDL
iii. One roof jack equals 30 feet EDL
* (12 ft length x 1.25 alum. flex)
+ 15 ft elbow + 30 ft wall cap = 60 ft EDL. This is the equivalent
duct length (or resistance) the fan must overcome to move air
through the duct to the outside.
- See the Fan
Sizing Charts for appropriate Panasonic model.
i. Select correct ACH chart for the application
ii. Find the intersect of the Square Feet and EDL to determine
the approriate Panasonic model(s). When values are not exact move
to next higher value
* 100 sq ft by 60 ft EDL = FV-15VQ3
Performance Curve Method
A ventilating fan's performance is plotted on a graph called a performance
curve. The performance curve shows airflow in cubic feet per minute
(CFM) along the horizontal axis and static pressure (resistance)
along the vertical axis. Figure A shows how a performance curve
works. The fan with a "Closed duct" has high static pressure
and no airflow; and the fan the "No duct" has low static
pressure and high airflow. In reality, an installed fan will be
somewhere in between these two points.

This method requires two calculations and plotting on a graph.
First is the Airflow (CFM) calculation, which calculates cubic feet
and the required CFM for the area to be ventilated. The second is
the Static Pressure (resistance) calculation, which calculates the
Equivalent Duct Length (EDL) of a straight duct run from the inlet
to the termination (outside) point of the building. Third, the results
of the airflow and static pressure calculations are then plotted
on the performance curve of ventilating fan models to find the ideal
model for a given application and duct run.
Example: Sizing for an 8 ft x 12 ft x 8 ft ceiling
bathroom using 12-foot long, 4 inch diameter aluminum flex duct,
one elbow, one wall cap.
- Airflow (CFM) Calculation
First calculate area in cubic feet (lenth x width x ceiling height).
Then divide this number by 60 to get the Cubic Feet per Minute
(CFM) required to replenish the entire air volume in one hour.
Next, multiply the CFM value by the appropriate ACH value for
the given application
i. 8 ft x 12 ft x 8 ft = 768 cubic feet
ii. 768 / 60 = 12.8 CFM value
iii. 12.8 x 8 ACH
* 102 CFM for intermittent bathroom ventilation
- Static Pressure (Resistance) Calculation
The Static Pressure calculation provides EDL and adjusts for airflow
resistance caused by duct material, elbows, and termination devices.
i. 12 ft flex aluminum duct x 1.25 = 15 feet EDL
ii. Once elbew equals 15 feet EDL
iii. One roof jack equals 30 feet EDL
* 15 + 15 + 30 = 60 feet total EDL
This is the equivalent duct length (or resistance) the fan must
over come to move air through the duct to the outside.
- Airflow and Static Pressure on Performance Curve Chart
The next step is to identify a fan that will provide 102 CFM at
60EDL. Figure B shows the performance curve for a Panasonic model
FV-15VQ3. First, find 60 EDL then drop straight dodwn to the horizontal
axis to determine the CFM's delivered at 60 EDL.

Example:
i. Locate the point on the blue "FAN" curve at 60 ft.
In this case, it is a point on the blue fan curve between the
yellow "50 ft" and the blue "75 ft" lines.
ii. From this point on the FAN line move straight down to the
horizontal axis to read CFM. In this case, it is close to 100
CFM.
* Therefore, a Panasonic FV-15VQ3 is the appropriate model
iii. Repeat Step 3. You may need to repeat Step 3 on the performance
curve for different fan models until you find a model that matches
the desired CFM and EDL.
Performance Curves can be found in the product spec sheet link
( ) next
to each model.
Back to top |
| |
The third step is to measure the Equivalent Duct Length of the
planned duct run. This requires a basic understanding of static
pressure caused by a duct run design and its components.
Static Pressure and Duct Run:
A ventilating fan must overcome resistance when pushing air from
the inlet, through the duct, to the outside of the building. This
resistance is known as static pressure. The amount of static pressure
depends on the duct length, type of duct, elbows and the roof jack
or wall cap.
Equivalent Duct Length:
Static pressure in a typical duct run is caused by the type of duct
material, elbows, exterior wall cap, etc. The table below shows
the standard values for duct components. The EDL chart allows you
to calculate the equivalent straight duct length in order to overcome
static pressure caused by each component in a duct run. The EDL
helps assure the fan performs as expected under the flow resistance
caused by the components listed in this chart.

Back to top |